AlarmMail Facility

  • Post author:
  • Reading time:4 mins read
  • Post comments:0 Comments

The AlarmMail facility is a background process which controls the automated dispatch of alert e-mails to specified users (User Name) mail accounts (Mail Address).


AlarmMail command line options

-IDisplay Configuration Interface
-wInclude Warning and Alarm messages
-cInclude Clear messages
-p secsSleep Period: Interval between reads of alarm database:Default 10
-m minsHoldoff Period: Identical messages within this period are ignored:Default 10
-dDebug mode
-hDisplay help

Configuration Interface (AlarmMail -I)

The configuration interface allows enabling of specific alert message types for specified addresses. After settings are edited and saved the AlarmMail process will re-read the configuration database and apply the changes. Subsequent generated alert messages are sent to those users enabled to receive such messages. .

The alert types are as follows :

1. Alerts A, C, D and G – Exceedance.

2. Alert B – Ellipse Boundaries.

3. Alert F – Step Change

4. Alert H – Gradient

5. Alert P – Prodict

Alert A :- Level Exceedance

Five warning amplitude levels and five alarm amplitude levels are available for each dynamic channel of each plant item. They correspond to the alert levels for each of the first 4 orders and the overall level.

Alert B :- Ellipse Boundary

A warning and alarm elliptical boundary are available for each of the first 4 orders. Boundaries are defined in terms of the ellipse centre (X_ref,Y_ref), the length of the major and minor axes (major, minor) and the orientation angle of the major axis (angle).

Alert C :- Non-synchronous vibration not measured in the standard components

A warning and alarm difference level are available for each dynamic channel of each plant item. The measurement is the difference between the overall level and the summation of the amplitude levels of the first 4 orders and the subsynchronous component.

Alert D :- Subsynchronous Amplitude Level

Identical to Alert A but corresponding to the subsynchronous component.

Alert F :- Step Change

A warning and alarm level corresponding to changes in the average level for each of the first 4 orders and the overall level.

Alert G :- Special Order Alert

Identical to Alert A but corresponding the special fifth order. This may be any order and by default is 5. Care must be taken when specifying this order (using Config process) as the highest order available is dictated by the number of samples acquired per revolution of the plant item.

Alert H :- Gradient Alert

The user specifies the maximum gradient for a particular channel and parameter over a specified bnumber of days. If the average rate of increase for that channel and parameter is found to be greater than that specified then an alarm is generated.

Alert P :- Proclass Alert

A multi-parameter enhancement to the elliptical boundary alarms described above (Alert B ). Historical data is analysed and machine states identified using Bayesian classification techniques for multiple static channels. For each of these states vibration data is identified and alarm boundaries calculated.

The following two tabs change content below.
Specialists in systems for acoustic and vibration measurement, analysis, and testing within the automotive, aerospace, defence, manufacturing, and power industries. The company designs and develops its own products and its engineers have decades of experience in solving real-world noise and vibration problems for major organizations throughout the world.